What Size Generator Do You Need to Run a Welder? (2026)
Start with the welder’s nameplate input rating
The data plate on the back of the welder, or the specifications table in its manual, lists rated input volts and rated input amps. Multiply them. A 120V welder rated at 20A input needs 120 x 20 = 2,400 volt-amps at full output. A 240V welder rated at 30A input needs 240 x 30 = 7,200 volt-amps. A 240V welder rated at 50A input needs 240 x 50 = 12,000 volt-amps.
That figure is the load at the welder’s maximum output. At lower amperage the machine draws less, so a 140A-class MIG welder run at 90A pulls well under its nameplate current. Size for the highest setting you will actually use on the job, not the highest the dial allows, and leave headroom above it. A generator loaded to its limit runs hot, burns fuel faster and gives you a sagging, unstable arc.
Estimating the load when you only know the output amperage
Some listings state only welding output amps. Welding standards use a conventional load voltage for each process: stick is 20 + 0.04 x amps, MIG is 14 + 0.05 x amps, and TIG is 10 + 0.04 x amps. Multiply that voltage by the output amps to get output watts.
Examples: MIG at 140A is 14 + 7 = 21V, so 21 x 140 = 2,940W of arc power. Stick at 90A is 20 + 3.6 = 23.6V, so about 2,124W. DC TIG at 150A is 10 + 6 = 16V, so 2,400W. Input power is higher than output power because the machine loses energy as heat. For a rough planning figure, divide output watts by 0.8, so the 140A MIG example lands near 3,700W of input. Treat that as an estimate and replace it with the nameplate number whenever you have it. Machines without power factor correction draw more current per watt of output than ones with it, which is another reason the plate figure beats any formula.
Generator size by welder type
These ranges follow from the nameplate arithmetic above. They are starting points; confirm against your welder’s manual.
- 120V MIG or flux-core with 15A input: 1,800VA at full output. A generator with at least 2,500 running watts leaves margin.
- 120V MIG, stick or TIG with 20A input: 2,400VA. Plan on 3,000 to 3,500 running watts, and make sure the generator has a 20A receptacle, not only 15A ones.
- 240V MIG or multiprocess welder with 30A input: 7,200VA. A generator rated about 8,000 running watts or more with a 240V outlet of at least 30A.
- 240V welder with 50A input: 12,000VA. This is portable-generator territory at the top end, or an engine-driven welder instead.
- Plasma cutters: use the nameplate input for the cutting current you need. A shop air compressor feeding the torch is a separate load with a starting surge, so do not count it as part of the same budget unless the plasma cutter has its own internal compressor.
A 3,500W generator can run a 120V welder drawing up to about 20A of input. It cannot run a 240V welder drawing 30A, which needs more than twice that power.
Inverter generator versus open-frame generator
An inverter generator produces AC, converts it to DC and then rebuilds a stable AC waveform electronically. That gives a cleaner sine wave and lets the engine speed follow the load. For welding, the clean waveform matters because the welder’s own electronics are sensitive to voltage and frequency swings, and many manuals state the voltage and frequency range the machine tolerates. Check the welder’s manual and the generator’s stated waveform distortion before pairing them.
Get inverter generatorThe trade-off is output per dollar and per pound. Inverter generators in the 2,000 to 4,000W range are easy to carry but often top out at 120V outlets, with a few 240V models above that. Open-frame generators deliver more watts for the money and commonly include a 240V receptacle, but their waveform is less clean and the engine runs at a fixed speed. For a 120V MIG or stick machine on remote jobs, an inverter generator is usually the easier fit. For a 240V welder, shop the receptacle first and the wattage second.
Receptacles, 240V and cord ends
The generator’s plug pattern has to match the welder’s cord. A common 240V pairing is a welder with a NEMA 6-50 plug on a generator that has a NEMA 14-50 or L14-30 outlet, and those patterns are not interchangeable. Do not cut off a plug or build a homemade adapter to force a match. Use a manufacturer-listed adapter or have the plug replaced to a pattern the welder’s manual allows.
Check two numbers on the generator’s panel: the receptacle amp rating and the breaker. A 120V 20A receptacle caps out at 2,400W no matter how large the generator is. A 30A receptacle at 240V tops out at 7,200W. If the generator’s panel lists a total running wattage, that total is shared across all outlets, so do not run lights, a grinder and a welder off it at once and expect each to get its full rating. Also check that the generator’s 120V and 240V outlets are not mutually limited: some models give you full 240V power only when the 120V outlets are idle.
Extension cord gauge for a generator-fed welder
Wire gauge is American Wire Gauge, where a smaller number is a thicker conductor. Common retail cord ratings are 14 AWG for 15A, 12 AWG for 20A and 10 AWG for 30A, and the rating is printed on the jacket. The longer the run, the more voltage drops. The drop in a single-phase cord is 2 x length in feet x resistance per foot x amps. Copper resistance is about 2.5 ohms per 1,000 feet for 14 AWG, 1.6 for 12 AWG and 1.0 for 10 AWG.
Worked example at 20A: a 50-foot 12 AWG cord drops 2 x 50 x 1.6 x 20 / 1,000 = 3.2V out of 120V. A 50-foot 10 AWG cord drops 2.0V. A 100-foot 14 AWG cord at 15A drops 7.5V, which is enough to hurt arc stability and strain the welder. A 12/3 extension cord is a practical choice for a 20A 120V welder over a short run. A 10/3 extension cord gives more margin for longer runs or when the generator will be loaded near its limit. Keep the cord as short as the job allows and put the length on the welding leads rather than the power cord where you can. Never coil a cord that is carrying heavy current, since the coil heats up.
Get 10/3 extension cord Get 12/3 extension cordFailure modes buyers hit
Undersized generator. The engine bogs when the arc strikes, the output voltage sags, and the welder may shut down on undervoltage. Fix it by sizing to the nameplate input, not the output amps.
Economy mode left on. Eco or idle-control settings let the engine drop its speed when load is light. On some generators this causes a lag when an arc starts. Turn it off for welding if the generator’s manual recommends it.
Altitude and heat. Small engines lose output at elevation and in hot weather. The generator manual lists a derating guide. If you weld at altitude, buy the next size up.
Fuel and runtime. A generator rated for hours at half load may run much shorter at full load. Check the load chart in the manual rather than the headline runtime.
Cord overheating. A thin or damaged cord, or a coiled one, gets warm or hot. Stop and replace it with a thicker gauge. A warm plug is a sign the receptacle or cord is undersized.
Related guides
- 110V vs 220V Welders (2026): Which Voltage Do You Actually Need?
- Arccaptain vs YesWelder (2026): Which Budget Welder Brand?
- Angle Grinders for Welding: Choose by Task, Power, and Safety (2026)
- Best Angle Grinders for Welding and Metal Fabrication (2026)
FAQ
Can a 3500 watt generator run a welder?
It can run a 120V welder whose nameplate input is up to about 20A, which is 2,400VA, if the generator has a 20A outlet. It cannot run a 240V welder with a 30A input, which needs 7,200VA. Check the welder’s rated input amps and volts and multiply them.
Do I need an inverter generator to run a welder?
Not always, but many welder manuals state a voltage and frequency tolerance, and an inverter generator holds a cleaner waveform than most open-frame units. Read the welder manual for what it accepts and the generator spec for its waveform distortion before buying.
What extension cord gauge should I use between a generator and a welder?
Match the cord rating to the welder’s input current. A 12 AWG cord is rated for 20A and a 10 AWG cord for 30A on common retail cords. Keep it short, because a long thin cord drops voltage; 100 feet of 14 AWG at 15A drops about 7.5V.